Fire Alarm Systems | FMC‑210‑SM Single Action Call Points
FMC‑210‑SM Single Action Call Points
Alarm triggering by breaking of the glass pane
▶
▶
Automatic or manual detector addressing via rotary
switch possible
Indicator LED for alarm or for inspection evaluation
▶
▶
Call point query routines with evaluation and multiple
transmission
Individual call point identification
▶
▶
Maintains LSN loop functions in the event of wire
interruption or short-circuit thanks to two integrated
isolators
The FMC‑210‑SM Single Action Call Points are used for
manual triggering, and can be used in the Local
SecurityNetwork LSN and LSN improved. The
FMC‑210‑SM Single Action Call Points are designed for
indoor deployment.
Individual call point identification with display of the call
point address on the fire panel ensures the quick location
of the triggered call point.
Certifications and Approvals
FMC‑210‑SM‑G‑R applies to
Functions
EN 54‑11:2001/A1:2005
•
5
EN 54‑17:2005
•
1
1
Region
Germany
Europe
Certification
VdS
2
G 207008 FMC-210-SM-G-R
4
CPD
0786-CPD-20316 FMC-210-SM-G-R
3
3
2
Installation/Configuration Notes
With single action call points, the alarm is triggered when
the glass plate (2) is broken and the button (3) springs
up.
Manual call points must be mounted visibly along
escape and rescue routes (e. g. exits, passageways,
stairwells) and be easily accessible.
An installation height of 1400 mm ±200 mm, measured
from the middle of the manual call point to the floor,
must be maintained.
•
•
This activates the microswitch for alarm triggering and the
indicator LED (4) blinks.
Manual call points must be adequately illuminated by
sunlight or another light source (including emergency
lighting if present).
•
The call point (3) can be reset after inserting a new glass
pane (2) and closing the door of the single action call
point (1). The indicator LED (4) goes out.
This does not reset the alarm on the fire panel.
FMC‑210‑SM Single Action Call Points | 3
Environmental Considerations
Protection class as per EN 60529 IP 52
Permissible operating temperature -10 °C. . . +55 °
Ordering Information
FMC‑210‑SM‑G‑B Form G, Blue
Single Action Call Point for indoor use, direct
triggering (type A), for LSN improved
FMC-210-SM-G-B
FMC-210-SM-G-R
FMC‑210‑SM‑G‑R Form G, Red
Single Action Call Point for indoor use, direct
alarm triggering (type A), for LSN improved
Accessories
FMX‑FSO‑LSN Punched, Self-adhesive Foil
Sets (Blank)
FMX-FSO-LSN
For the labeling field of manual call points of
the Series FMC‑210.
1 unit = 10 sheets
FMC‑FST‑DE Printed Labeling Foils for the
Upper Label Field
FMC-FST-DE
For yellow and blue manual call points of Ser-
ies FMC‑120 and FMC‑210, 1 unit = 5 sheets
FMC‑SPGL‑DEIL Spare Glasses
For manual call points of Series DM, DKM,
SKM, FMC‑120 and FMC‑210.
1 unit = 5 spare glasses
FMC-SPGL-DEIL
FMM-KEY-Form G/H
Key for Fire Detectors Types G and H
made of red plastic (ASA)
4 | FMC‑210‑SM Single Action Call Points
Americas:
Europe, Middle East, Africa:
Bosch Security Systems B.V.
P.O. Box 80002
5600 JB Eindhoven, The Netherlands
Phone: + 31 40 2577 284
Fax: +31 40 2577 330
Asia-Pacific:
Robert Bosch (SEA) Pte Ltd, Security Systems
11 Bishan Street 21
Singapore 573943
Phone: +65 6258 5511
Fax: +65 6571 2698
Represented by
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, New York, 14450, USA
Phone: +1 800 289 0096
Fax: +1 585 223 9180
© Bosch Security Systems 2011 | Data subject to change without notice
T3892227979 | Cur: en-US, V16, 9 Jun 2011
|