MARCH 2000
SW980AE
SW981AE
SW982AE
SW980A
SW981A
SW982A
Local/Remote Electronic Switches
1
O
2 T
/ REMOTE
SW
LOCAL
ITCH
R
®
B
BLACK BOX
REMOTE
724-746-5500
A
B
A
R
PW
CUSTOMER
SUPPORT
INFORMATION
Order toll-free in the U.S. 24 hours, 7 A.M. Monday to midnight Friday: 877-877-BBOX
FREE technical support, 24 hours a day, 7 days a week: Call 724-746-5500 or fax 724-746-0746
Mail order: Black Box Corporation, 1000 Park Drive, Lawrence, PA 15055-1018
Web site: www.blackbox.com
•
E-mail: [email protected]
LOCAL/REMOTE ELECTRONIC SWITCHES
NORMAS OFICIALES MEXICANAS (NOM)
ELECTRICAL SAFETY STATEMENT
INSTRUCCIONES DE SEGURIDAD
1. Todas las instrucciones de seguridad y operación deberán ser leídas antes de
que el aparato eléctrico sea operado.
2. Las instrucciones de seguridad y operación deberán ser guardadas para
referencia futura.
3. Todas las advertencias en el aparato eléctrico y en sus instrucciones de
operación deben ser respetadas.
4. Todas las instrucciones de operación y uso deben ser seguidas.
5. El aparato eléctrico no deberá ser usado cerca del agua—por ejemplo, cerca
de la tina de baño, lavabo, sótano mojado o cerca de una alberca, etc.
6. El aparato eléctrico debe ser usado únicamente con carritos o pedestales que
sean recomendados por el fabricante.
7. El aparato eléctrico debe ser montado a la pared o al techo sólo como sea
recomendado por el fabricante.
8. Servicio—El usuario no debe intentar dar servicio al equipo eléctrico más allá
a lo descrito en las instrucciones de operación. Todo otro servicio deberá ser
referido a personal de servicio calificado.
9. El aparato eléctrico debe ser situado de tal manera que su posición no
interfiera su uso. La colocación del aparato eléctrico sobre una cama, sofá,
alfombra o superficie similar puede bloquea la ventilación, no se debe colocar
en libreros o gabinetes que impidan el flujo de aire por los orificios de
ventilación.
10. El equipo eléctrico deber ser situado fuera del alcance de fuentes de calor
como radiadores, registros de calor, estufas u otros aparatos (incluyendo
amplificadores) que producen calor.
11. El aparato eléctrico deberá ser connectado a una fuente de poder sólo del
tipo descrito en el instructivo de operación, o como se indique en el aparato.
2
NOM STATEMENT, TRADEMARKS
12. Precaución debe ser tomada de tal manera que la tierra fisica y la polarización
del equipo no sea eliminada.
13. Los cables de la fuente de poder deben ser guiados de tal manera que no
sean pisados ni pellizcados por objetos colocados sobre o contra ellos,
poniendo particular atención a los contactos y receptáculos donde salen del
aparato.
14. El equipo eléctrico debe ser limpiado únicamente de acuerdo a las
recomendaciones del fabricante.
15. En caso de existir, una antena externa deberá ser localizada lejos de las lineas
de energia.
16. El cable de corriente deberá ser desconectado del cuando el equipo no sea
usado por un largo periodo de tiempo.
17. Cuidado debe ser tomado de tal manera que objectos liquidos no sean
derramados sobre la cubierta u orificios de ventilación.
18. Servicio por personal calificado deberá ser provisto cuando:
A: El cable de poder o el contacto ha sido dañado; u
B: Objectos han caído o líquido ha sido derramado dentro del aparato; o
C: El aparato ha sido expuesto a la lluvia; o
D: El aparato parece no operar normalmente o muestra un cambio en su
desempeño; o
E: El aparato ha sido tirado o su cubierta ha sido dañada.
TRADEMARKS USED IN THIS MANUAL
Any trademarks used in this manual are acknowledged to be the property of the trademark
owners.
3
LOCAL/REMOTE ELECTRONIC SWITCHES
Contents
Chapter
Page
1. Specifications ............................................................................................. 5
2. Introduction ............................................................................................... 7
3. Installation and Configuration ................................................................. 8
3.1 Before You Install ................................................................................ 8
3.2 The Setup Procedure .......................................................................... 9
4. Operation ................................................................................................. 17
4.1 Local Switching ................................................................................. 17
4.1.1 ABC and ABCDE Switches (SW980 and SW982 Units) ........ 17
4.1.2 X Switches (SW981 Units) ...................................................... 18
4.2 Remote Switching ............................................................................. 19
4.2.1 ABC and ABCDE Switches (SW980 and SW982 Units) ........ 19
4.2.2 X Switches (SW981 Units) ...................................................... 19
4.3 Test Results ........................................................................................ 22
5. Troubleshooting ...................................................................................... 23
5.1 Calling Black Box .............................................................................. 23
5.2 Shipping and Packaging ................................................................... 23
4
CHAPTER 1: Specifications
1. Specifications
Compliance —
Data Rate —
FCC Part 15 Subpart J Class A, IC Class/classe A
Up to 256 kbps typical; higher speeds possible with
careful consideration of cabling and equipment
requirements
User Controls —
All models: Remote switching either through TTL,
RS-232, RS-422/485, or other active drivers or
through dry-contact closure;
SW980 and SW982 models: (1) Rear-mounted
2-position DIP switch for grounding;
SW981 models: (2) Rear-mounted 2-position DIP
switches for grounding
Indicators —
Front-mounted LEDs:
All models: (1) for Power;
SW980 models: (2) for Active Port;
SW981 models: (1) for Straight, (1) for Crossed;
SW982 models: (4) for Active Port
Connectors —
All models: (1) Rear-mounted RJ-45 female,
(1) Internal 4-position terminal block;
SW980 models: (3) Rear-mounted DB25 female;
SW981 models: (4) Rear-mounted DB25 female;
SW982 models: (5) Rear-mounted DB25 female
Leads Supported — DB25: All
Signal Levels —
Between 15 VDC maximum for all leads
“On” Resistance
Through Switch —
SW980 and SW981 models: 35 ohms maximum,
22 ohms typical;
SW982 models: 100 ohms maximum, 40 ohms typical
Port-to-Port
Switching Speed
Using Remote
Inputs —
Less than 1 µs
5
LOCAL/REMOTE ELECTRONIC SWITCHES
Remote Input
Logic Levels —
VIH greater than 2.5 volts, maximum +15 volts;
VIL less than 0.5 volts, minimum –15 volts
NOTE
For dry-contact operation, the total external-
connection DC resistance must be less than
240 ohms when the dry contact is closed for the
Local/Remote Electronic Switch to correctly
read this condition as a “low” input.
Power —
SW980A, SW981A, SW982A:
From wallmount power supply PS154:
Input: 120 VAC, 60 Hz;
Output: 17 VAC CT;
SW980AE, SW981AE, SW982AE:
From wallmount power supply PS154E:
Input: 230 VAC, 50 Hz;
Output: 17 VAC CT;
Consumption: 1 watt
MTBF —
65,000 hours
Operating
Temperature —
32 to 140˚F (0 to 60˚C)
Storage
Temperature —
–4 to +158˚F (–20 to +70˚C)
Up to 95% noncondensing
High-impact plastic
Humidity —
Enclosure —
Size —
SW980 and SW981 models: 2.5"H x 6"W x 6.3"D
(6.4 x 15.2 x 16 cm);
SW982 models: 3.5"H x 6"W x 6.3"D
(8.9 x 15.2 x 16 cm)
Weight —
1.5 lb. (0.7 kg)
6
CHAPTER 2: Introduction
2. Introduction
Switching between data lines manually can often damage the connected
equipment, because this relatively slow and imprecise action can cause data-line
surges and spikes large enough to damage today’s sensitive circuitry. With the
Local/Remote Electronic Switches, you can eliminate this potential hazard. Their
electronic switching action provides surgeless, spikeless changeovers—something
a mechanical switch just can’t do.
In addition, these switches can be controlled remotely, from a convenient
out-of-sight location.
The stock models available are:
SW980A
SW980AE 230-VAC 2-to-1 Switch
SW981A 115-VAC “X” (2-to-2) Switch
SW981AE 230-VAC “X” (2-to-2) Switch
SW982A 115-VAC 4-to-1 Switch
115-VAC 2-to-1 Switch
SW982AE 230-VAC 4-to-1 Switch
These Switches can also be cascaded to allow a larger number of ports
to be switched.
7
LOCAL/REMOTE ELECTRONIC SWITCHES
3. Installation and Configuration
3.1 Before You Install
Check the box and its contents before you begin installing your Local/Remote
Electronic Switch. You should have received one Switch unit, one AC power supply,
and one copy of this manual. If you didn’t receive all of these items, or if they have
sustained damage that does not seem to be shipping-related, notify Black Box right
away. If they have sustained impact or water damage that seems to have happened
during shipping, notify both Black Box and the shipping carrier immediately.
Unpack the box carefully. We recommend that you save the original container
and its packing materials in case you need to ship the Switch later.
You’ll need to install the Switch within 6 feet (1.8 m) of an AC outlet. Also,
keep the Switch away from water and extreme temperatures.
Make sure you have the proper cables or adapters. Whatever interface you want
to switch (RS-232, RS-422, RS-485, V.35, TTL, etc.), you must use either cables with
DB25 male connectors or adapters that convert the interface from your cables’
connectors to DB25 male connectors. To perform remote switching, you must use
an appropriate length of cable that has at least four wires. If you intend to connect
it to the Switch’s internal terminal block, this cable must be unterminated at the
Switch end. If you intend to connect it to the Switch’s “REMOTE” connector, this
cable must have wires pinned to Pins 3 through 6 of a male RJ-45 connector at the
Switch end. (If you must use existing cables that do not meet these requirements,
call Black Box Technical Support; we might be able to provide adapters or create
a special product for you.)
8
CHAPTER 3: Installation and Configuration
3.2 The Setup Procedure
Installing and configuring a Local/Remote Electronic Switch is relatively quick and
easy, and will vary only slightly depending on which model you’ve chosen. Follow
these steps:
(Steps 1 through 4 are for remotely switched applications only:)
1. Make sure that the Switch is unplugged (is not receiving AC power). Open
the Switch by unscrewing the two screws on the bottom of the unit (save these
screws) and removing the top of the unit’s housing. (You will probably have
to peel back the CE sticker on the bottom of the unit to get at one of the
screws.)
2. Find jumper W1 (for SW980 or SW981 units) or jumpers W2 and W3 (for
SW982 units) on the Switch’s circuit board. Refer to Figure 3-1 on the next
page if your unit is an SW980 model, to Figure 3-2 on page 11 if your unit is
an SW981 model, or to Figure 3-3 on page 12 if your unit is an SW982 model.
Set the jumper(s) as appropriate for your application:
• Set W1, or W2 and W3, to the A-B position for applications that use
dry-contact closure to perform remote switching.
• Set W1, or W2 and W3, to the B-C position for applications that use
active driver(s) to perform remote switching.
(text continued on page 13)
9
LOCAL/REMOTE ELECTRONIC SWITCHES
W1
A
B
C
TB1
REAR
FRONT
Figure 3-1. PCB layout of the SW980 models.
10
CHAPTER 3: Installation and Configuration
TB1
A
B
C
W1
REAR
FRONT
Figure 3-2. PCB layout of the SW981 models.
11
LOCAL/REMOTE ELECTRONIC SWITCHES
W2
TB1
A
B
C
W3
A
B
C
FRONT
REAR
Figure 3-3. PCB layout of the SW982 models.
12
CHAPTER 3: Installation and Configuration
(text continued from page 9)
3. If you will be performing remote switching using a cable that is unterminated
at the Switch end, attach the cable’s wires to the appropriate positions of the
4-position terminal block labeled “TB1” (refer to Figures 3-1 through 3-3 on
pages 10 through 12 and to Tables 4-1 and 4-2 on pages 20 and 21). Connect
the ground of the remote driver, or one side of the dry contact, to (either of)
the terminal block’s ground pin(s). Connect the remote driver’s output(s),
or the other side of the dry contact, to the terminal block’s input pin(s).
4. Close the Switch’s housing and screw the two screws you removed in step 1
back in. If you are using a remote-switching cable that is unterminated at the
Switch end, make sure that the cable is seated in the slot on the left side of
the Switch’s rear panel before you put the cover back on.
(The installation procedure for locally switched applications begins with Step 5:)
5. Find DIP switch S2 (for SW980 and SW982 units) or DIP switches S2 and S3
(for SW981 units) on the Switch’s rear panel. Refer to Figure 3-4 below or
Figure 3-5 or 3-6 on the next page, which show the rear panels of the SW980,
SW981, and SW982 models respectively.
B
A
SERIAL
PARALLEL
C
REMOTE
Figure 3-4. Rear panel of the SW980 models.
13
LOCAL/REMOTE ELECTRONIC SWITCHES
B
A
BB
AA
SERIAL
PARALLEL
REMOTE
Figure 3-5. Rear panel of the SW981 models.
B
A
D
SERIAL
PARALLEL
REMOTE
C
E
Figure 3-6. Rear panel of the SW982 models.
14
CHAPTER 3: Installation and Configuration
6. Set the DIP switch(es) as appropriate for your application. Refer to Table 3-1
and Figure 3-7 below, and keep in mind that OFF = UP and ON = DOWN.
Table 3-1. Possible Settings for Switches S2 and S3
All 25 leads of the Local/Remote Electronic Switch’s DB25 connectors are straight-
through and are isolated from one another. In RS-232 and DB25 parallel applications,
we recommend that you use DIP switches S2 and S3 to make a “common” ground
connection; this will help eliminate intermittent noise problems.
Recommended Settings for RS-232 Applications:
S2
S3
Model(s)
SW980/982 units ON
Pos. 1 Pos. 2 Pos. 1 Pos. 2 Connection(s) Made
OFF
N/A
N/A
Port C Pin 7 to
Switch ground
(down) (up)
SW981 units
ON
ON
OFF
OFF
(up)
Ports AA and BB Pin 7
to Switch ground
(down) (down) (up)
Recommended Settings for DB25 Parallel Applications:
S2
S3
Model(s)
SW980/982 units OFF ON
Pos. 1 Pos. 2 Pos. 1 Pos. 2 Connection(s) Made
N/A
ON
N/A
Port C Pin 18 to
Switch ground
(up)
(down)
SW981 units
OFF OFF
ON
Ports AA and BB Pin 18
to Switch ground
(up)
(up)
(down) (down)
Recommended Settings for Other Applications:
All models—Set all positions of switches S2 [and S3] to OFF (up).
SERIAL
PARALLEL
(S3)
(S2)
ON 1
2
ON 1
2
(S2)
ON 1
2
SERIAL
PARALLEL
Figure 3-7. DIP switch S2 of the SW980 and SW982 models (left)
and DIP switches S2 and S3 of the SW981 models (right).
15
LOCAL/REMOTE ELECTRONIC SWITCHES
7. Put the Switch in the site you’ve selected.
8. Shut off the equipment you plan to connect to the Switch.
9A. SW980 and SW982 units only: Connect the cable from the “common” device
(the one that’s going to access—or be shared by—the other devices) to the
common connector (marked “C”) on the Switch’s rear panel. Connect the
cables from the “branch” devices (those that will share—or be intermittently
accessed by—the other device) to the branch connectors (marked “A” and
“B” [and “D” and “E” on the SW982]) on the Switch’s rear panel.
9B. SW981 units only: Connect the cables from the two “source” devices to the
connectors on the Switch’s rear panel labeled “A” and “B.” Connect the
cables from the “destination” devices to the connectors on the Switch’s
rear panel labeled “AA” and “BB.”
10. Remotely switched applications using terminated cable only: Plug the cable’s RJ-45
plug into the connector marked “REMOTE” on the Switch’s rear panel. Make
sure that the appropriate wires are attached to the appropriate pins in the
RJ-45 plug (refer to Tables 4-1 and 4-2 on pages 20 and 21). The ground of
the remote driver, or one side of the dry contact, must be connected to the
connector’s ground pin. The remote driver’s output(s), or the other side of
the dry contact, must be connected to the connector’s input pin(s).
11. Plug the Switch’s power supply into an AC outlet.
12. Turn on the attached equipment.
Your Local/Remote Electronic Switch should now be ready for continuous
operation, but test it to make sure it has been installed properly. See Chapter 4.
16
CHAPTER 4: Operation
4. Operation
4.1 Local Switching
4.1.1 ABC AND ABCDE SWITCHES (SW980 AND SW982 UNITS)
Refer to Figure 4-1 below: Test your Local/Remote Electronic Switch system by
having the common device send data to, or receive data from, branch devices “A”
and “B” (and, for SW982 units, “D” and “E”), one after the other. Switch between
branch devices by manually turning the knob on the Switch’s front panel.
ABC SWITCH
SWITCHED
A
COMMON
C
SWITCHED
B
Connections made are AC and BC -“C” IS COMMON
ABCDE SWITCH
SWITCHED
A
SWITCHED
B
COMMON
C
SWITCHED
D
SWITCHED
E
Connections made are AC, BC, DC, and EC-“C” is COMMON
Figure 4-1. Switching in the SW980 (top) and SW982 (bottom) models.
17
LOCAL/REMOTE ELECTRONIC SWITCHES
4.1.2 X SWITCHES (SW981 UNITS)
Refer to Figure 4-2 below: Test your Local/Remote Electronic Switch system by
having each source device (“A” and “B”) send data to each destination device
(“AA” and “BB”), one after the other. Switch between data pathways by manually
turning the knob on the Switch’s front panel.
“X” SWITCH
A
B
AA
BB
Connections made are A-AA & B-BB or A-BB & B-AA
Figure 4-2. Switching in the SW981 models.
18
CHAPTER 4: Operation
4.2 Remote Switching
When you do remote switching, keep these things in mind:
• The knob on the Switch’s front panel must be in the “REMOTE” position.
• The Switch interprets any voltage more negative than approximately 1.4 volts
as a “low” and any voltage more positive than approximately 1.4 volts as a
“high” (see the “Remote Input Logic Levels” spec in Chapter 1 for maximum
and minimum switching points).
• In dry-contact applications, the Switch will read a “low” when the contact
is closed and a “high” when the contact is open.
• The maximum allowed voltage on the remote-input leads is 15 volts.
4.2.1 ABC AND ABCDE SWITCHES (SW980 AND SW982 UNITS)
To test the remote-switching capability of your Local/Remote Electronic Switch
system, you must first turn the knob on the Switch’s front panel to “REMOTE.”
Now have the common device send data to, or receive data from, branch devices
“A” and “B” (and, for SW982 units, “D” and “E”), one after the other. Switch
between branch devices by sending “high” and “low” electric signals to the Switch
through its RJ-45 connector or its internal 4-position terminal block. See Tables 4-1
and 4-2 on pages 20 and 21 for pinouts and signal levels; see Figure 4-1 on page 17
for basic illustrations of how the Switches function.
4.2.2 X SWITCHES (SW981 UNITS)
To test the remote-switching capability of your Local/Remote Electronic Switch
system, you must first turn the knob on the Switch’s front panel to “REMOTE.”
Now have each source device (“A” and “B”) send data to each destination device
(“AA” and “BB”), one after the other. Switch between data pathways by sending
“high” and “low” electric signals to the Switch through its RJ-45 connector or its
internal 4-position terminal block. See Table 4-1 on the next page for pinouts and
signal levels; see Figure 4-2 on the previous page for a basic illustration of how the
Switch functions.
19
LOCAL/REMOTE ELECTRONIC SWITCHES
Table 4-1. Connector Pinouts and Signal Levels for
Port Selection with the ABC Switch (SW980 Models) or
Path Selection with the X Switch (SW981 Models)
Pinout of the RJ-45 Connector
1
2
3
4
5
6
7
8
N/C
N/C
N/C
Remote input
+5 VDC output
Signal ground
N/C
N/C
Pinout of the 4-Position Terminal Block
1
2
3
4
Signal ground
N/C
Remote input
Signal ground
Signal Levels for Port Selection (SW980 Models)
Port Selected
Remote Input
A
B
High
Low
Signal Levels for Path Selection (SW981 Models)
Paths Selected
Remote Input
A to AA, B to BB (straight)
B to AA, A to BB (crossed)
High
Low
20
CHAPTER 4: Operation
Table 4-2. Connector Pinouts and Signal Levels for
Port Selection with the ABCDE Switch (SW982 Models)
Pinout of the RJ-45 Connector
1
2
3
4
5
6
7
8
N/C
Reserved for future use
Remote input B
Remote input A
+5 VDC output
Signal ground
N/C
N/C
Pinout of the 4-Position Terminal Block
1
2
3
4
Signal ground
Remote input B
Remote input A
Reserved for future use
Signal Levels for Port Selection
Port Selected
Remote Input A
Remote Input B
A
B
D
E
High
Low
High
Low
High
High
Low
Low
21
LOCAL/REMOTE ELECTRONIC SWITCHES
4.3 Test Results
If data doesn’t seem to be getting through when a device on one side of the Switch
is connected to a device on the other side of the Switch, make sure that:
• Both devices are turned on and receiving power.
• The Switch is receiving power (its “POWER” LED should be lit).
• The Switch’s front-panel knob is set properly.
• All cables are good and cable connections are secure.
• Any software involved is configured and operating correctly.
If your Switch is working properly, your system is ready to go. If the Switch fails
the test, or if it should begin malfunctioning later, contact Black Box Technical
Support (see Chapter 5).
22
CHAPTER 5: Troubleshooting
5. Troubleshooting
5.1 Calling Black Box
If you determine that your Local/Remote Electronic Switch is malfunctioning,
do not attempt to alter or repair the unit. It contains no user-serviceable parts. Call
Black Box Technical Support at 724-746-5500.
Before you do, make a record of the history of the problem. We will be able to
provide more efficient and accurate assistance if you have a complete description,
including:
• the nature and duration of the problem;
• when the problem occurs;
• the components involved in the problem;
• any particular application that, when used, appears to create the problem
or make it worse; and
• the results of any testing you’ve already done.
5.2 Shipping and Packaging
If you need to transport or ship your Local/Remote Electronic Switch:
• Package it carefully. We recommend that you use the original container.
• If you are returning the Switch, please include everything you received with it.
If you are shipping the Switch for repair or return, contact Black Box to get a
Return Authorization (RA) number.
23
NOTES
© Copyright 2000. Black Box Corporation. All rights reserved.
1000 Park Drive • Lawrence, PA 15055-1018 • 724-746-5500 • Fax 724-746-0746
|